4.3 
        
        
        
        
        
        57 Google reviews
      
      Specifications of Microtek 3In-1out Online Ups 25Kva
 Model 
                     Supermax-Series - I 
                     Capacity 
                     5KVA to 30KVA 
                     Technology 
                     Double Conversion high Freq. Switching PWM, using IGBT's 
                     Input Voltage  
                     160V AC~270V AC ±5V AC, Single Phase for upto 10KVA and 360V AC~450V AC ±5V AC, Three Phase for upto 30KVA 
                     Frequency 
                     45~55Hz 
                     Phase 
                     Single phase upto 10KVA and Three Phase from 5 to 30KVA 
                     Generator Compatibility 
                     Present 
                     Output Voltage 
                     230V Ac ±1% 
                     Frequency Range 
                     50Hz ± 0.5% 
                     THD (Liner Load) 
                     <3% 
                     THD (Non-Liner Load) 
                     <5% 
                     Overload Capability 
                     	
125% for 2minuted / 150% for 30Seconds 
                     Crest Factor 
                     	
3:1 (max) 
                     Shot Circuit Protection 
                     	
Instant 
                     Waveform 
                     Pure Sine Wave 
                     Manual Bypass 
                     Inbuilt upto 15KVA 
                     Static Bypass (optional) 
                     <5ms 
                     Inverter Efficiency 
                     ? 90% on rated full load 
                     Overall Efficiency 
                     ? 80% 
                     DC Voltage 
                     180 / 360 VDC 
                     Mimic Control Panel 
                     LED for UPS status and LCD for Voltage, Current & Frequency 
                     Audible Alarm 
                     For Battery Low / DC High / Output High / Overload 
                     Noise Level 
                     ? 50dB 
                     Transient Response 
                     For 100% step load charge, ± 5% and recovers to normal within 20 miliseconds. 
                     Ambient Temperature / Relative Humidity 
                     	
0-45° C / 0-95% Non-Condensing 
                     Cooling 
                     Forced Aircooled 
                    
 
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 